| MODEL |
|
The
storage tank shall be a Hanson Tank built to ASME Boiler & Pressure Vessel
Code Sect. IV HLW, or Sect. VIII, Div 1 for unfired pressure vessels,
bear a "HLW" or "U" stamp, and be registered with the National Board
when required. |
| PRESSURE |
|
Design working pressure shall be _________ psi (125 psi standard).
(160 psi max if HLW). |
| SIZE |
|
Vessel diameter shall be ________ inches with a length of ________ inches. |
| CAPACITY |
|
Nominal capacity shall be ________ U.S. gallons. |
| LININGS |
|
Shall be lined per Hanson Tank spec with: |
|
|
_________ FDA approved Epoxy |
|
|
_________ Glass with anodes (HLW only) |
|
|
_________ Cement (Hanson "Cemcoat") |
|
|
_________ Other: ________________ |
| CONFIGURATION |
|
Configuration shall be: |
|
|
_________ Vertical with angle legs |
|
|
_________ Horizontal with: _______ saddles _______ welded feet. |
| CONNECTIONS |
|
Service connections shall be ________ inch nominal pipe size. |
|
|
________ threaded ________ flanged |
|
|
Plus FNPT connections for drain, thermometer, relief valve, aquastat, etc. |
EXTERIOR Standard:
Optional:
Optional: |
|
________ Power buff per SSPC SP1/3 plus(1) coat 2/3 mil primer.
________ Sandblast plus(1) coat 2/3 mil primer. (Std with glass).
________ Sandblast plus(1) coat 2/3 mil zinc rich primer.
|
| INSULATION |
|
Shall be insulated per Hanson specification: |
| (Optional) |
|
________ # FI 1190 Foam with hard-shell topcoat, R - ________ |
|
|
________ # JI 1093 Fiberglass with metal jacket, R - ________ (Insulation cannot be used in conjunction with loose saddles) |
| HEATER |
|
Shall have a _______ inch nominal diameter heater collar, with |
| (Optional) |
|
a ________" x________" heater bundle installed |
|
|
________ Single Wall ________ Double Wall |
| |